Abstract
The NACE work group on "Deaerator Operation and Water Chemistry" (Work Group T-7H-7b) developed a questionnaire on basic deaerator design, operating history, and water chemistry. A survey was conducted to determine the suitability of this questionnaire and if useful information could be obtained from a limited survey. The data obtained on 84 deaerators inspected by the wet fluorescent magnetic particle method indicates that water hammer is a very likely cause of deaerator cracking. Other factors may be significant, but they were not revealed by this survey.
© 1986 Association for Materials Protection and Performance (AMPP). All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise) without the prior written permission of AMPP. Positions and opinions advanced in this work are those of the author(s) and not necessarily those of AMPP. Responsibility for the content of the work lies solely with the author(s).