Abstract
In 1995, there were two failures in the 20.000 BPD HF Alky unit at the Amuay Refinery causing a shutdown of the unit. The failures occurred in one flange and one weld in the depropanizer charge carbon steel pipe, containing propane, isobutane and anhydrous hydrofluoric acid at 190 F (88 C) and 321 psig (22.5 Kg/cm2). Examination showed severe uniform corrosion at the inside surface of the flange while the adjacent elbow showed minimal corrosion loss. The other failure showed preferential attack in the weld without corrosion loss in the pipe components.
A complete evaluation of the Alky plant was necessary to identify other lines in similar conditions that could cause future emergency shutdown of the unit. An extensive on stream inspection program was performed on critical lines of the unit. This paper summarizes the results and conclusions of this evaluation.